31 researched codes and status messages; 2 require model-specific verification. A code alone is not proof of a failed component.
E01Service fault
Long freeze cycle logged.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE02Service fault
Long harvest cycle logged.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE03Event history
Input-power loss recorded after power interruption.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Source explicitly marks Event Log only / No Alarm. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE04Service fault
Condenser temperature high; air-cooled / water-cooled interpretation depends on configuration.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE05Service fault
High-pressure cutout switch opened.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE07Service fault
Temperature pattern indicates a starved TXV / low-charge condition; cause requires diagnosis.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE08Service fault
TXV malfunction indication for the applicable dual-circuit configuration.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT Dual-circuit variant only.
Scope: Controller Event Log record; not proof of a failed part. Dual-circuit variant only. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE09Service fault
Evaporator 1 flooding condition reported.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE10Service fault
Evaporator 2 flooding indication for applicable dual-TXV / dual-circuit configuration.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT Dual-circuit variant only.
Scope: Controller Event Log record; not proof of a failed part. Dual-circuit variant only. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE11Service fault
Refrigeration system failed the expected temperature-change check.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE12Service fault
Curtain switch open / bin-full condition persisted more than 12 hours.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE15Service fault
Low liquid-line temperature / low-ambient fan-cycle-control condition.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE16Service fault
Remote-condenser temperature condition.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT Remote-condenser variant only.
Scope: Controller Event Log record; not proof of a failed part. Remote-condenser variant only. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE19Service fault
Ice-thickness probe signal outside its expected range.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE20Service fault
Water-system fault condition; multiple sensing / cycle criteria can trigger it.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE21Service fault
T1 temperature-sensor reading outside the valid range.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE22Service fault
T2 temperature-sensor reading outside the valid range.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE23Service fault
T3 temperature-sensor reading outside the valid range.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE24Service fault
T4 temperature-sensor reading outside the valid range.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE25Service fault
Low bin-level probe sensor fault.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT Optional bin-level probe only.
Scope: Controller Event Log record; not proof of a failed part. Optional bin-level probe only. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE26Service fault
Middle bin-level probe sensor fault.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT Optional bin-level probe only.
Scope: Controller Event Log record; not proof of a failed part. Optional bin-level probe only. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE27Service fault
High bin-level probe sensor fault.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT Optional bin-level probe only.
Scope: Controller Event Log record; not proof of a failed part. Optional bin-level probe only. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE28Event history
Selected optional AuCS cleaning accessory was not detected.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT Optional AuCS only.
Scope: Source explicitly marks Event Log only / No Alarm. Optional AuCS only. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE29Event history
USB communication event for engineering purposes.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Source explicitly marks Event Log only / No Alarm. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE30Event history
USB download event for engineering purposes.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Source explicitly marks Event Log only / No Alarm. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE31Event history
Timed fallback / Safe Mode based on recent successful cycles.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Source explicitly marks Event Log only / No Alarm. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE32Service fault
RS485 communication fault recorded.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE33Service fault
Keyboard fault recorded.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE34Service fault
Display fault recorded.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc legacy Indigo R290, STH038 05/12 controller; US 60 Hz configuration only, not NXT
Scope: Controller Event Log record; not proof of a failed part. E06/E13/E14/E17/E18 are spare entries and excluded. Thresholds are not transferred to Indigo NXT.
Manufacturer / technical referenceE01Model check
Meaning requires model-specific verification
Unverified reference context: Owner guide groups this label under Service Fault / safety-limit troubleshooting; its individual meaning is not established by this source.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc Indigo NXT; matching owner-guide family, exact SKU context to confirm
Scope: The source mentions E01 or E02 together. Legacy Indigo R290 definitions / thresholds have not been copied into this NXT row.
Manufacturer / technical referenceE02Model check
Meaning requires model-specific verification
Unverified reference context: Owner guide groups this label under Service Fault / safety-limit troubleshooting; its individual meaning is not established by this source.
What to do: Record full model/suffix, control revision, complete code / LED cadence, mode and sequence. Use the matching owner guide. Persistent faults require qualified service; the indication does not prove one part has failed.
Applies to: Manitowoc Indigo NXT; matching owner-guide family, exact SKU context to confirm
Scope: The source mentions E01 or E02 together. Legacy Indigo R290 definitions / thresholds have not been copied into this NXT row.
Manufacturer / technical referenceNo matching records. Check the model, display characters or beep/LED pattern and the matching owner guide.